Since the distribution system exhibits a large X/R ratio, there may be a high possibility of convergence issue for the Newton Raphson load flow analysis. In this regard, the power flow analysis is conducted using the backward forward sweep load flow method. The base power is taken as 100 MVA, whereas the base voltage is considered to be 12.66 kV.
In this study, the DIG and SC are incorporated, and to reflect the practical aspect of system planning, the load growth is considered at 3% annually. The planning horizon is taken to be 10 years. However, unlike most literature, the planning is not conducted in a single stage. Here, the planning horizon is divided into two planning stages as described below:
Planning Stage 1: System planning for 0-5 years.
Planning Stage 2: System planning for 6-10 years.
In each planning stage, DIG and SC are integrated in the system according to the load quantity, and to do a detailed analysis, different planning scenarios are considered as given below, which will assist the distribution system operator in finding the best planning option for their system.
Table 1: Different scenarios that are taken into account in this study.
Devices
|
Scenarios
|
1
|
2
|
3
|
4
|
DIG
|
NC
|
C
|
NC
|
C
|
SC
|
NC
|
NC
|
C
|
C
|
C: Considered; NC: Not Considered
In this study, an improved version of the PSO algorithm is used as an optimization technique for allocating DIG and SC. In the standard PSO, the weighting factor ‘w’ is taken as a constant. But, in the improved version, w is varied linearly from its maximum value to the minimum value. The maximum and minimum value of ‘w’ is taken as 0.9 and 0.4, respectively. The value of other tuning parameters of PSO i.e. C1 and C2 are taken as 1.7. The maximum number of iteration is taken as 100 and the population number is chosen to be 200. The maximum number of iteration is set as the convergence criteria.
A. Optimum Deployment Results
The optimal location, optimal size, and the values of the objective functions namely VPEI, ALRI, PLRI, and CI for the 1st planning stage are given in Table 2. In scenario 2, the optimal locations of DIG are obtained as bus 12 and 30 with a capacity of 975.3 KW and 1045.8 KW whereas in scenario 3, the optimal locations of SC are found to be bus 11 and 30 with a capacity of 509.9 KVAr and 943.3 KVAr, respectively. On the other hand, in scenario 3, both the device are integrated simultaneously and the obtained locations of DIG and SC are buses {12, 30} and buses {26, 33}, respectively. The optimal sizes of these devices are attained as {942.7, 1010.3} KW, {927.9, 494.1} KVAr. The objective values of different scenarios also indicate that the values of VPEI are increased, whereas the values of ALRI and RLRI decrease in all the scenarios. This represents that these devices improve voltages and reduce losses and it is evident from the table that scenario 4 i.e. both the device simultaneously incorporated provide the highest benefits. However, the values of CI indicate that the maximum value is obtained in the case of scenario 3. Moreover, the value of CI is less than 1 in the case of scenario 2, which indicates that this scenario is not beneficial for planning as evident from an economic standpoint. Comparing scenarios 2 and 3, it can be concluded that scenario 2 provides better results for VPEI, ALRI, and RLRI, establishing the superiority of DIG over SC.
The optimal location, optimal size, and the values of the objective functions namely VPEI, ALRI, PLRI, and CI for the 2nd planning stage are given in Table 2. It is clear from the table that the obtained values of optimal locations in planning stage 2 are mostly different from what was obtained in planning stage 1. The objective values of different scenarios also indicate that the values of VPEI are increased, whereas the values of ALRI and RLRI decrease in all the scenarios. This represents that these devices improve voltages and reduce losses and it is
Table 2: Optimal allocation results for Planning Stage 1.
Scenarios
|
Optimal location
|
Optimal
Size
|
VPEI
|
ALRI
|
RLRI
|
CI
|
Scenario 1
(BASE CASE)
|
-
|
-
|
1.0000
|
1.0000
|
1.0000
|
1.0000
|
-
|
-
|
Scenario 2
(WITH DIG)
|
12
|
975.3
|
1.3776
|
0.3986
|
0.4077
|
0.9516
|
30
|
1045.8
|
Scenario 3
(WITH SC)
|
11
|
509.9
|
1.2259
|
0.7116
|
0.7143
|
10.4551
|
30
|
943.3
|
Scenario 4
(WITH DIG & SC)
|
12
|
942.7
|
1.4142
|
0.1682
|
0.1892
|
1.1951
|
30
|
1010.3
|
26
|
927.9
|
33
|
494.1
|
Table 3: Optimal allocation results for Planning Stage 2.
Scenarios
|
Optimal location
|
Optimal
Size
|
VPEI
|
ALRI
|
RLRI
|
CI
|
Scenario 1
(BASE CASE)
|
-
|
-
|
1.0000
|
1.0000
|
1.0000
|
1.0000
|
-
|
-
|
Scenario 2
(WITH DIG)
|
6
|
1956.5
|
1.5906
|
0.345
|
0.3711
|
1.588
|
24
|
1065.1
|
Scenario 3
(WITH SC)
|
24
|
557.4
|
1.3969
|
0.6913
|
0.6918
|
14.7713
|
26
|
333.2
|
Scenario 4
(WITH DIG & SC)
|
7
|
1581.7
|
1.6837
|
0.3004
|
0.3451
|
1.8849
|
24
|
1158.3
|
10
|
1407.6
|
33
|
236
|
Table 4: Detailed Economic Analysis for different Planning Stages.
|
Planning Stages
|
Investment (A)
|
Benefit (B)
|
Net Savings (B-A)
|
CI (B/A)
|
Scenario 1
(BASE CASE)
|
Stage 1
|
0
|
0
|
0
|
-
|
Stage 2
|
0
|
0
|
0
|
-
|
Net (1+2)
|
0
|
0
|
0
|
-
|
Scenario 2
(WITH DIG)
|
Stage 1
|
1897701
|
1805921
|
-91780
|
0.9516
|
Stage 2
|
2837045
|
4505369
|
1668324
|
1.5880
|
Net (1+2)
|
4734746
|
6311290
|
1576544
|
1.3330
|
Scenario 3
(WITH SC)
|
Stage 1
|
43596
|
455811
|
412215
|
10.4553
|
Stage 2
|
25893
|
382472
|
356579
|
14.7713
|
Net (1+2)
|
69489
|
838283
|
768794
|
12.0635
|
Scenario 4
(WITH DIG & SC)
|
Stage 1
|
1839654
|
2404125
|
564471
|
1.3068
|
Stage 2
|
2580904
|
4864525
|
2283621
|
1.8848
|
Net (1+2)
|
4420558
|
7268650
|
2848092
|
1.6443
|
|
evident from the table that scenario 4 i.e. both the device simultaneously incorporated, provides the highest benefits. However, the values of CI indicate that the maximum value is obtained in the case of scenario 3. Unlike planning stage 1, the value of CI in a scenario in the 2nd planning stage is obtained more than 1, which indicates a financial benefit of the distribution company in utilizing this scenario for system planning. Similar to the 1st planning stage, scenario 2 provides better results for VPEI, ALRI and RLRI as compared to scenario 1, establishing the superiority of DIG over SC.
B. Detailed Economic Analysis
The obtained values of CI as given in Tables 2-3 indicate that CI is attained to be the highest in the case of SC. As described in subsection 3.B, CI is a ratio of total benefit and total investment. To find out the economic feasibility of the devices, it is important to calculate net saving after the planning horizon is over. Accordingly, a detailed analysis of the economic performance is performed stage-wise for different scenarios, as shown in Table 4, in terms of investment, benefit, net savings, and CI. The investment is the highest in scenario 1 due to a higher penetration level of DIG, whereas the investment is the lowest for scenario 2, which is because of the lower installation cost of SC. Table 4 clearly shows that in 1st planning stage, the investment is more as compared to the savings in the case of DIG incorporation only. Therefore, the net saving is negative in this case. However, in the 2nd planning stage, there is a positive value of net saving for the case of DIG. Analyzing the table, it can be concluded that the highest value of net saving considering both the planning stages is obtained for scenario 4, indicting the economic superiority of incorporating these devices in the system simultaneously.
C. Analysis of different scenarios based on Voltage profile, line loss, and power flow
1st and 2nd planning stage is illustrated in Figures 4 and 5, respectively. These figures indicate that in the base case when there are no devices in the system, the voltage profile is very worse for both the planning stages. However, with the incorporation of DIG and SC, voltage profile is improved for almost all the buses and the voltage magnitudes tend to reach the nominal value of 1 P.U. As compared to the case of Sc, DIG presents a better enhancement of voltage profile. However, for both the planning stages, the voltage profile improvement is the highest when both the devices are incorporated simultaneously in the distribution system. Moreover, it is important to note that due to more increment of load in planning stage 2, the voltage magnitudes became less in stage 2.
A comparative analysis between different considered scenarios based on active and reactive power losses is also conducted and the graphical representation of active and reactive power losses is shown in Figures 6 and 7, respectively, for planning stages 1 and 2. The reduction of both the losses is more in scenario 2 as compared to scenario 3, which indicates more loss reduction capability of DIG over SC. It can also be noted that the values of active and reactive power losses are more in planning stage 2 as compared to planning stage 1 due to the increment of the load value.
In this study, the planning horizon is considered to be 10 years and a yearly load growth of 3% is taken into account. Hence, the power flow is a matter of concern for the distribution company and in this regard, a power flow analysis is carried out in the presence of these devices. The active and reactive power flow for different scenarios in the 1st planning stage is indicated in Figures 8 and 9, respectively, whereas the power flow in planning stage 2 is indicated in Figures 10 and 11.
Figures 8 and 10 indicate that with the incorporation of DIG, there is a significant reduction of active power flow through most of the feeders since DIG can act as a local power source and provide active power to the local loads. On the other hand, when only SC is incorporated in the system, there is not a significant reduction of active power. The small amount of reduction in active power is due to the active loss reduction by SC. The highest reduction of active power flow is possible with the simultaneous incorporation of DIG and SC.
Figures 9 and 11 indicate that with the incorporation of SC, there is a significant reduction of reactive power flow through most of the feeders since SC can act as a local power source and provide reactive power to the local loads. On the other hand, when only DIG is incorporated in the system, there is not a significant reduction of reactive power since there is no reactive power output from DIG. The small amount of reduction in reactive power is due to the reactive loss reduction by DIG. Moreover, the highest reduction of reactive power flow is possible with the simultaneous incorporation of DIG and SC.
D. Convergence Characteristics
The convergence characteristics of the proposed improved PSO for different scenarios is shown in Figures 12 and 13, respectively for planning stage 1 and 2. In both the figures, the PSO algorithm converges to the minimum value when DIG and SC are incorporated simultaneously. Therefore, this scenario provides maximum potential benefits to the system owner. However, these figures clearly show that the number of iteration the optimization technique takes to converge is the highest for the case of simultaneous incorporation of DIG and SC. This is because the size of the problem becomes more when both the devices are incorporated simultaneously and accordingly, it takes more iteration to converge. On the other hand, the converge value of F indicates overall more benefit of DIG as compared to SC. Further, these figures also indicate that the number of iteration to converge is more in the case of DIG as compared to SC for both the planning stages.