The single line diagram of the transmission line network used as a case study is as shown in Fig. 7. A brief description of each of the components modelled in the MATLAB/ SIMULINK environment is presented in the sub section that follows.
4.4 The Static Var Compensator (SVC) Simulink and control model
The distance relay model explored is as shown in Fig. 9 comprises of the fault locator, mho circle characteristics graph, impedance measurement black, zone detection block, fault detection and identification block.
The SVC model incorporated into this research work is shown below in Fig. 10. It was designed by Pierre Giroux and Gibert Sybille (Hydro-Quebec). SVCs are shunt-connected devices responsible for voltage profile correction and reduction of transmission line losses. The model designed by the authors was used to investigate the effect of harmonics, transients and stresses on power components during fault situations. The model’s voltage and frequency parameters were revised in order to align with the requirements of this research.
Table 1 outlines the results obtained when the SVC is connected and disconnected from a short transmission line of 18.4km for both faults in zone 1 and zone 2. The analysis in Table 1 was based on the simulation of five different types of faults on the power grid network considering zone 1 and zone 2. For example, in zone 1, considering a Single Line-to-Earth fault, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected with the transmission line is shown in Fig. 11 (a) while Fig. 11 (b) shows the Resistance-Reactance (R-X) diagram for the distance relay when SVC is not connected for the same L-E type of fault. Figure 11a and Fig. 11b clearly show plotted points at different magnitudes of Resistance and Reactance as shown in Table 1 for both Line-to-Earth faults with and without the SVC connected to the bus. Consequently, with SVC connected and SVC disconnected the distance relay was observed to have tripped at 11.49 km and 8.311 km respectively. Thus, indicating that during single-line-to-earth fault conditions, the distance relay over-reaches with the SVC connected.
The controlled firing of the thyristors in order to coordinate the addition or reduction of VAR in the system is done by the SVC control system. The SVC Control system comprises of four modules which includes the distribution unit, measurement system, firing unit, and voltage regulator [8]–[10]. The simulations were carried out considering faults occurring in zone 1 and zone 2 of the distance protective relay.
Table 1
Simulation result for the impedance and fault location for a 18.4km short line as seen by the distance relay modelled in MATLAB/Simulink
Protection zone | SVC connection status | | Type of faults |
| | | L-E fault | L-L fault | L-L-L fault | L-L-E fault | L-L-L-E fault |
zone 1 | with svc | apparent impedance | 0.7067 + j1.594 | 0.7067 + j1.594 | 0.7067 + j1.594 | 1.006 + j1.992 | 0.7067 + j1.594 |
fault location | 11.49 km | 11.49 km | 11.49 km | 14.70 km | 11.49 km |
zone 1 | without svc | apparent impedance | 0.4075 + j1.194 | 0.7067 + j1.594 | 0.7067 + j1.594 | 1.006 + j1.992 | 0.7067 + j1.594 |
fault location | 8.311 km | 11.49 km | 11.49 km | 14.70 km | 11.49 km |
summary for zone 1 distance relay | Over reach | Same | Same | Same | Same |
zone 2 | with svc | apparent impedance | 2.482 + j5.539 | 2.472 + j5.029 | 2.472 + j5.029 | 2.482 + j5.042 | 2.482 + j5.042 |
fault location | 39.99 km | 36.92 km | 36.92 km | 37.03 km | 37.03 km |
zone 2 | without svc | apparent impedance | 2.482 + j5.539 | 2.473 + j5.029 | 2.473 + j5.029 | 2.482 + j5.042 | 2.482 + j5.042 |
fault location | 39.99 km | 36.92 km | 36.92 km | 37.03 km | 37.03 km |
summary for zone 2 distance relay | Same | Same | Same | Same | Same |
When the simulation was carried out for other types of shunt faults such as Double-Line-to-Earth fault, Phase-to-Phase faults, Three-Phase-to-Earth faults, the Resistance -Reactance (R-X) diagram for the distance relay when SVC is connected and not connected remains the same. Table 1 shows the results for Double-Line-to-Earth fault, Phase-to-Phase faults, Three-Phase-to-Earth faults with and without the SVC connected to the bus. The results presented shows that the distance relay tripped at 11.49 km. The implication of this is that during these faults conditions with SVC connected or not connected, the distance relay fault location accuracy is not affected.
Similarly, for zone 2, when the simulation was carried out for all types of shunt faults such as single Line to earth fault, Double-Line-to-Earth fault, Phase-to-Phase faults, Three-Phase-to-Earth faults, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected and not connected remains the same as shown in Fig. 12. Table 1 shows the results for single Line to earth fault, Double-Line-to-Earth fault, Phase-to-Phase faults, Three-Phase-to-Earth faults with and without the SVC connected to the bus. Consequently, for all the shunts mentioned above, the distance relay was observed to have tripped at 39.99 km, 37.03 km, 36.92 km and 37.03 for their respective fault types. Thus, indicating that during single Line to earth fault, Double-Line-to-Earth fault, Phase-to-Phase faults, Three-Phase-to-Earth faults conditions with SVC connected or not connected, the distance relay fault location accuracy is not affected.
Table 2 outlines the results obtained when the SVC is connected and disconnected from a medium length transmission line of 100km for both faults in zone 1 and zone 2. The analysis in Table 2 was based on the simulation of five different types of faults on the power grid network considering zone 1 and zone 2. For example, in zone 1, considering the Three-Phase-to-Earth fault and Three-Phase faults, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected with the transmission line is shown in Fig. 13 (a) while Fig. 13 (b) shows the Resistance-Reactance (R-X) diagram for the distance relay when SVC is not connected for the same Three-Phase-to-Earth fault. Figure 13a and Fig. 13b clearly shows plotted points at different magnitudes of Resistance and Reactance as shown in Table 2 for both Three-Phase-to-Earth fault and Three-Phase faults with and without the SVC connected to the bus. Therefore, with SVC connected and SVC disconnected the distance relay was observed to have tripped at 73.52 km and 80.00 km respectively. Thus, indicating that the distance relay under-reaches with the SVC connected for Three-Phase-to-Earth fault and Three-Phase faults.
When the simulation was carried out for other types of shunt faults such as Single-Line-to-Earth fault, Double-Line-to-Earth fault and Phase-to-Phase faults the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected and not connected remains the same. Table 2 shows the results for Single-Line-to-Earth fault, Double-Line-to-Earth fault and Phase-to-Phase faults with and without the SVC connected to the bus. Consequently, for all the shunt faults mentioned above, the distance relay was observed to have tripped at approximately 80.00 km. Thus, indicating that during Single-Line-to-Earth fault, Double-Line-to-Earth fault and Phase-to-Phase faults conditions with SVC connected or not connected, the distance relay fault location accuracy is not affected.
Table 2
Simulation result for the impedance and fault location for a 100km medium line as seen by the distance relay modelled in MATLAB/Simulink
Protection zone | SVC connection status | | Type of faults |
| | | L-E fault | L-L fault | L-L-L fault | L-L-E fault | L-L-L-E fault |
zone 1 | with svc | apparent impedance | 5.467 + j10.840 | 5.467 + j10.820 | 4.869 + j10.040 | 5.467 + j10.820 | 4.869 + j10.040 |
fault location | 80.00 km | 79.85 km | 73.52 km | 79.87 km | 73.52 km |
zone 1 | without svc | apparent impedance | 5.467 + j10.840 | 5.467 + j10.840 | 5.467 + j10.840 | 5.467 + j10.840 | 5.467 + j10.840 |
fault location | 79.97 km | 79.97 km | 80.00 km | 79.98 km | 80.00 km |
summary for zone 1 distance relay | Same | Same | under reach | Same | under reach |
zone 2 | with svc | apparent impedance | 2.858 + j9.139 | 2.858 + j9.139 | 2.858 + j9.139 | 2.229 + j30.37 | 2.858 + j9.139 |
fault location | 63.09 km | 63.09 km | 63.09 km | 200.6 km | 63.09 km |
zone 2 | without svc | apparent impedance | 4.466 + j21.41 | 4.466 + j21.41 | 4.466 + j21.41 | 4.466 + j21.41 | 4.466 + j21.41 |
fault location | 144.1 km | 144.1 km | 144.1 km | 144.1 km | 144.1 km |
summary for zone 2 distance relay | under-reach | under-reach | under-reach | over-reach | under-reach |
Considering zone 2, for Single Line-to-Earth fault, Phase-to-Phase faults and three-Phase-to-Earth faults, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected with the transmission line is shown in Fig. 14 (a) while Fig. 14 (b) shows the Resistance-Reactance (R-X) diagram for the distance relay when SVC is not connected for the same fault types mentioned above. Figure 14a and Fig. 14b clearly shows plotted points at different magnitudes of Resistance (R) and Reactance (X) for when the SVC is connected and disconnected. Subsequently, the distance relay, with SVC connected and disconnected was observed to have tripped at 63.09 km and 144.1 km respectively. Thus, indicating that the distance relay under-reaches with the SVC connected for Single Line-to-Earth fault, Phase-to-Phase faults and three-Phase-to-Earth faults.
Similarly, for zone 2, when the simulation was carried out for Double-Line-to-Earth fault, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected and not connected are observed to be different. Table 2 shows the results for a Double-Line-to-Earth fault with and without the SVC connected to the bus. Therefore, for a Double-Line-to-Earth fault with SVC connected and disconnected, the distance relay was observed to have tripped at 200.6 km, and 144.1 km respectively. Therefore, the distance relay over reaches with the SVC connected for Double-Line-to-Earth faults.
Table 3 outlines the results obtained when the SVC is connected and disconnected from a long transmission line of 226 km for both faults in zone 1 and zone 2. The analysis in Table 3 was based on the simulation of five different types of faults on the power grid network considering zone 1 and zone 2. For example, in zone 1, considering the Line-to-Earth fault, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected with the transmission line is shown in Fig. 15 (a) while Fig. 15 (b) shows the Resistance-Reactance (R-X) diagram for the distance relay when SVC is not connected for the same Line-to-Earth fault. Figure 15a and Fig. 15b clearly shows plotted points at different magnitudes of Resistance and Reactance as shown in Table 3 for all types of shunt faults with and without the SVC connected to the bus. Therefore, with SVC connected and SVC disconnected the distance relay was observed to have tripped at 174.30 km and 180.80 km respectively. Thus, indicating that the distance relay under-reaches with the SVC connected for Line-to-Earth faults.
When the simulation is carried out for other types shunt faults such as Double-Line-to-Earth fault, Three-Phase-to-Earth fault and Phase-to-Phase faults, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected and not connected under reaches for all shunt fault types mentioned above. Table 3 shows the results for Double-Line-to-Earth fault, Three-Phase-to-Earth fault and Phase-to-Phase faults with and without the SVC connected to the bus. Consequently, for all the shunts mentioned above, the distance relay was observed to have tripped at approximately 182.60 km, 181.90 km and 182.60 km respectively. Thus, indicating that during Double-Line-to-Earth fault, Three-Phase-to-Earth fault and Phase-to-Phase fault conditions with SVC connected or not connected, the distance relay fault location accuracy is affected.
Considering zone 2, for Double-Line-to-Earth faults, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected with the transmission line is shown in Fig. 16 (a) while Fig. 16 (b) shows the Resistance-Reactance (R-X) diagram for the distance relay when SVC is not connected. Figure 16a and Fig. 16b clearly shows plotted points at the different magnitude of Resistance (R) and Reactance (X) for when the SVC is connected and disconnected. Subsequently, the distance relay, with SVC-connected and disconnected was observed to have tripped at 250.40 km and 248.40 km respectively. Thus, indicating that the distance relay over-reaches with the SVC connected for Double-Line-to-Earth faults.
Similarly, for zone 2, when the simulation is carried out for Line-to-Earth faults, Three-Phase-tot-Earth fault, Phase-to-Phase faults, the Resistance-Reactance (R-X) diagram for the distance relay when SVC is connected and not connected are observed to be different. Table 3 shows the results for Double-Line-to-Earth fault with and without the SVC connected to the bus. Therefore, for Line-to-Earth faults, Three-Phase-tot-Earth fault, Phase-to-Phase faults, with SVC connected and disconnected, the distance relay was observed to have tripped at 250.40km and 235.50km, 250.40km and 247.80km, 250.40km and 247.80km respectively. Therefore, the distance relay over reaches with the SVC connected for all shunt type of faults as earlier mentioned.
Table 3
Simulation result for the impedance and fault location for a 226 km long line as seen by the distance relay modelled in MATLAB/Simulink
Protection zone | SVC connection status | | Type of faults |
| | | L-E fault | L-L fault | L-L-L fault | L-L-E fault | L-L-L-E fault |
zone 1 | with svc | apparent impedance | 11.76 + j23.70 | 11.76 + j23.70 | 11.76 + j23.70 | 11.76 + j23.70 | 11.76 + j23.70 |
fault location | 174.30 km | 174.30 km | 174.30 km | 174.30 km | 174.30 km |
zone 1 | without svc | apparent impedance | 12.36 + j24.50 | 12.00 + j24.98 | 12.36 + j24.50 | 12.00 + j24.98 | 12.12 + j24.81 |
fault location | 180.80 km | 182.60 km | 180.80 km | 182.60 km | 181.90 km |
summary for zone 1 distance relay | under-reach | under-reach | under-reach | under-reach | under-reach |
zone 2 | with svc | apparent impedance | 16.10 + j34.43 | 16.10 + j34.43 | 16.10 + j34.43 | 16.10 + j34.43 | 16.10 + j34.43 |
fault location | 250.40 km | 250.40 km | 250.40 km | 250.40 km | 250.40 km |
zone 2 | without svc | apparent impedance | 13.12 + j33.27 | 16.49 + j33.91 | 16.62 + j33.73 | 16.49 + j33.91 | 16.63 + j33.73 |
fault location | 235.50 km | 248.40 km | 247.80 km | 248.40 km | 247.80 km |
summary for zone 2 distance relay | over-reach | over-reach | over-reach | over-reach | over-reach |
4.6 Summary of results
The simulation result when a highly inductive load of 130MVAR is applied into the real-life scenario setting of Ikorodu-Sagamu 132kV transmission line settings being fed from a source of 600MVA short circuit is analyzed. The simulation result shows a case of very high voltage despite the highly inductive load due to the surplus amount of source power.
From the simulation results observed and documented for zone 1 and zone 2 in Table 1, Table 2, Table 3, Fig. 17(a), Fig. 17(b) and Fig. 17(c) the following observations were made when the known fault application points are varied directly with the short, medium and long lines considered in the simulation.
-
For short lines, when the SVC is applied, the simulation shows us that for both zone 1 and zone 2 faults, the SVC has little or no impact on the fault location as only single line to earth fault in zone 1 (10% of the total faults simulated) showed that the distance relay under reached when the SVC was connected. All other shunt type fault simulation carried out on the distance relay showed no cases of under reach or over reach.
-
For medium lines, when the SVC is applied, the simulation shows us that for both zone 1 and zone 2 faults, the SVC has a large impact on the fault location as all the shunt type of faults with the exception of single line to earth fault in zone 1, phase to phase fault in zone 1 and double line to earth fault in zone 1 (30% of the total faults simulated) showed that the distance relay under reached when the SVC was connected. The double line to earth fault in zone 2 was observed to have over reached when the SVC was connected.
-
For long lines, when the SVC is applied, the simulation shows us that for both zone 1 and zone 2 faults, the SVC has a large impact on the fault location as all the shunt type of faults under-reached for faults in zone 1 (100% of the total faults simulated). Thus, the distance relay under reached when the SVC was connected. In addition, for all shunt type of faults simulated in zone 2, the distance protection relays were observed to have over-reached for fault types when the SVC was connected.
Furthermore, the distance protective relays see these fault locations as either over-reach or under-reach. The over-reach and under-reach are evidence that error margins are introduced when SVCs are connected. Similarly, Fig. 17(a), Fig. 17(b) and Fig. 17(c) shows Bar charts for short, medium and long transmission lines respectively for the easy comparison for each fault type with and without SVC connected.
SVCs appear to have increasing effect on distance protective relays as the length of the transmission line is increased. The under-reach characteristics of the distance relay tends to be more consistent with the increase in the length of the transmission line. Figure 17(a), Fig. 17(b) and Fig. 17(c) shows graphically the under reach and over reach tendencies of the distance protective relays.